88 ~ 132VAC/176 ~264VAC selected by switch 249 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
83%
AC CURRENT (Typ.)
3A/115VAC 1.5A/230VAC
INRUSH CURRENT (Typ.)
COLD START 40A
LEAKAGE CURRENT
<3.5mA / 240VAC
PROTECTION
OVER LOAD
105 ~ 135% rated output power Protection type : Fold back current limiting, recovers automatically after fault condition is removed
OVER VOLTAGE
31 ~ 36.5V Protection type : Constant voltage limiting, recovers automatically after fault condition is removed
OVER TEMPERATURE
RTH5≧80℃ Detect on heatsink of Q1,Q2 power transistor Protection type : Shun down o/p voltage, recovers automatically after temperature goes down
BATTERY
ESC series with bat. polarity, bat. Under voltage, bat. Over voltage protection
FUNCTION
FAN CONTROL
NO FAN
ENVIRONMENT
WORKING TEMP.
-10 ~ +60℃(Refer to output load derating curve)
WORKING HUMIDITY
20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY
-20 ~ +85℃, 10 ~ 95% RH
VIBRATION
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY & EMC
SAFETY STANDARDS
CSA60950-1(UL3101-1,IEC1010-1,EN61010-1) Approved
WITHSTAND VOLTAGE
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
EMI CONDUCTION & RADIATION
Compliance to EN55022 (CISPR22) Class B
HARMONIC CURRENT
Compliance to EN61000-3-2,-3
EMS IMMUNITY
Compliance to EN61000-4-2,3,4; ENV50204, Light industry level, criteria A
OTHERS
MTBF
250.9K Hrs min.(ESP-120) MIL-HDBK-217F (25℃)
DIMENSION
150*140*86mm (L*W*H)
测试条件与备注4
All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
Tolerance : includes set up tolerance, line regulation and load regulation.
The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.